All manufacturing sectors are facing major challenges in the current climate: legislation is getting stricter, compliance increasingly expensive and international standards get ever more complex.

Energy use, a key parameter for cleanroom operators to factor, has seen new regulation and standards coming into play as governments look to curb CO2 emissions and energy wastage. The BS EN 16001, unveiled at the BSI Cleanroom Conference 2010, is the energy management standard that demands a greener ethos and yet puts commercial performance on the front line.

The BS EN 16001 is designed to ensure that systems are in place for continuous improvement in energy management. It guides cleanroom users to look at how they manage their energy usage and provides commercial benefits in terms of reduction in operational costs.

The cleanroom sector places a heavy requirement on HVAC; air handling units are frequently running 24/7. The wide use of HEPA filters and the need to control humidity and temperature also notch up energy consumption.

In the pharmaceutical and medical sectors energy-expensive processes have become enshrined in the standards and are rigorously enforced. However, what is the ‘science’ behind these cleanroom design benchmarks that have such an influence on the present day operational ‘norms’?

The development of cleanrooms in the past 50 years shows that many of the key pharma HVAC control parameters have their origins in the cleanroom technology of the 1960s developed for the electronics industry; in particular, the evolution of cleanrooms as a result of NASA’s space travel programme in the 1950s and 1960s.

It is generally accepted that during this period the now familiar term laminar flow was introduced, as well as the specification of 0.46 m/s air velocity and the requirement for 20 air changes per hour. These concepts appear in cleanroom guidelines, regardless of their relevance or effectiveness in different industry sectors.

Airflow and contamination control
There is a reasonable motive to challenge current contamination control recommendations without affecting operational effectiveness. Some parameters can be relaxed by using a risk-based approach to gather the required data to show there is no risk to product yield or safety. For example, what would the impact to the clean environment be if air velocity was reduced from 0.46 m/s to 0.30 m/s? The rule of thumb is as follows:

  • Grade A and B: 45 air changes/hour
  • Grade C: 30 air changes/hour
  • Grade D: 20 air changes/hour

All of that air needs to be conditioned, moved and filtered 24/7 and therefore energy consumption is a significant ongoing cost. How are these air change rates arrived at in terms of mitigating the risk of airborne contamination? They are not based on calculated suppression rates but based on historical fact that using those high air change rates will result in exceeding the cleanroom grade classification. Documented research by Whyte et al. on unidirectional airflow (UDF) areas at the Orthopaedic Unit at Glasgow University has shown that after a certain point increasing velocities did not achieve lower contamination levels.

There does not appear to be any published research exploring the net effect on contamination levels as a result of decreasing velocities and volumes. But, is it proven that contamination levels will increase with lower air velocities and air change rates?

Air movement within the cleanroom is fundamental in determining the optimum air velocities and visualisation experiments involving smoke tests are key to understanding this. Airflow visualisation is typically performed once the facility has been fully completed and set into the effective mode of operation. The results of airflow visualisation are reviewed to ensure a minimum sweep of air is achieved within the facility. Often the actual operational characteristics of the facility are far in excess of the minimum sweep expectations.

Airflow visualisation can lead to energy savings when adjustments to the facility HVAC system can be made, selecting a lower air volume flow rate that satisfies the minimum clean air sweep expectations. Computational fluid dynamic simulations can also be used to assess the suitability of clean air sweep patterns at certain predetermined air volume flow rates.

Opportunities for energy savings can also be found in the “out of hours set back” a strategy regularly used in office environments. Here, air changes are reduced in facilities, or unused parts of the facility, overnight or at weekends. The proviso being that airflow must remain high enough to maintain the correct pressure cascade and validated operational status must be resumed before activities recommenced. These actions are easier to achieve when considered at the design stage of a new facility, rather than retrospectively.

 Resources & Articles

CLIN ® "Resources" page is for individuals/companies seeking information on cleanrooms and controlled environments. Find Cleanroom News, Discussion Forums, Cleanroom Cleaning Recommendations, Cleanroom Terminology, Cleanroom Directory, and more.

 Content Disclaimer

Information are contributed by/from different websites and all credit goes to its respective owners/writers/websites/companies and etc, and while we endeavour to keep the information up to date and correct, we make no representations or warranties of any kind, express or implied, about the completeness, accuracy, reliability, suitability or availability with respect to the website or the information, products, services, or related graphics contained on the website for any purpose. Any reliance you place on such information is therefore strictly at your own risk.

In no event will we be liable for any loss or damage including without limitation, indirect or consequential loss or damage, or any loss or damage whatsoever arising from loss of data or profits arising out of, or in connection with, the use of this website.

Through this website you are able to link to other websites which are not under the control of respective owners/writers/websites/companies and etc. We have no control over the nature, content and availability of those sites. The inclusion of any links does not necessarily imply a recommendation or endorse the views expressed within them.

Every effort is made to keep the website up and running smoothly. However, CLIN ® takes no responsibility for, and will not be liable for, the website being temporarily unavailable due to technical issues beyond our control.

We are experienced in Cleanroom Solutions

Call Us for Consultation +6(04) 398 1778

About CLIN

Cleanroom Industries Sdn. Bhd. was founded in 1999 as a pioneer manufacturer in Malaysia specializing in design and manufacture of a full range of cleanroom-related architectural products for cleanroom applications up to Class 1 cleanliness.

Awards & Recognitions

ISO 9001 Malaysia Power Brand Super Excellent Brand Sirim QAS Made in Malaysia Asia Pacific International Honesty Enterprise Keris Award