Qualification of an aseptic processing facility is a complex project including qualification of the cleanrooms in the facility, IQ/OQ/PQ of the equipment and utilities in the facility, airflow visualization studies, personnel training and qualification, aseptic process simulations, process validation, conformance runs, and other validation activities. This article focuses on the activities involved in certification and qualification of the cleanroom itself.
Installation Qualification
Installation qualification activities for a new cleanroom typically include the following items:
- Verification that the materials of construction are as specified (e.g., Epoxy Terrazzo flooring, smooth hard walls compatible with cleaning chemicals such as phenolic compounds or sodium hypochlorite, etc.)
- Verification of adequate lighting (typically defined in user requirements) at work height
- Verification of appropriate installation of air handling units and ductwork or laminar flow units
- Verification that air handling ductwork has been adequately cleaned. This is very important, as improperly cleaned ductwork can cause HEPA leaks in some cases.
- Verification that the specified HEPA or ultra-low particulate air (ULPA) filters have been installed and installed properly Verification of location and size of returns
- Verification of instrumentation type, location, and installation
- Verification of installation of air handling units or laminar flow units.
Operational Qualification
Operational qualification for a clean room might include the following:
- Verification of proper operation of air handling units, humidifiers and dehumidifiers, duct heaters, smoke alarms, dampers, and other controls
- Verification of proper operation of the building management system (BMS) or other control system for the cleanroom
- Measurement of vibration and noise in the cleanroom
- Cleanroom classification activities
Cleanroom Qualification
Classification of a cleanroom is typically performed according to ISO 14644-1 and its supporting documents. Typical activities involved in classification of a cleanroom include the following:
- Certification of HEPA filters, as discussed in the previous column.
- Measurement of airflow velocity and airflow volume. For Grade A areas, airflow velocity is measured using an anemometer or micro manometer at several points across each filter.
- Air changes per hour are calculated by dividing the supply volume in cubic feet or cubic meters per hour by the room volume in cubic feet or cubic meters.
- Measurement of differential pressures between rooms. This is typically accomplished using an electronic micromanometer or differential pressure gauge.
- Particulate classification is performed per ISO 14644-1 and its associated documents, using a standard discrete particle counter (DPC). Each room in the complex should be verified as meeting the ISO Class or EU Grade for the activities performed in that room.
- Airflow visualization. This is performed in all Grade A processing areas to demonstrate that the airflow is appropriate for aseptic processing. Airflow visualization will be the topic of an upcoming column.
Resources & Articles
CLIN ® "Resources" page is for individuals/companies seeking information on cleanrooms and controlled environments. Find Cleanroom News, Discussion Forums, Cleanroom Cleaning Recommendations, Cleanroom Terminology, Cleanroom Directory, and more.
Content Disclaimer
Information are contributed by/from different websites and all credit goes to its respective owners/writers/websites/companies and etc, and while we endeavour to keep the information up to date and correct, we make no representations or warranties of any kind, express or implied, about the completeness, accuracy, reliability, suitability or availability with respect to the website or the information, products, services, or related graphics contained on the website for any purpose. Any reliance you place on such information is therefore strictly at your own risk.
In no event will we be liable for any loss or damage including without limitation, indirect or consequential loss or damage, or any loss or damage whatsoever arising from loss of data or profits arising out of, or in connection with, the use of this website.
Through this website you are able to link to other websites which are not under the control of respective owners/writers/websites/companies and etc. We have no control over the nature, content and availability of those sites. The inclusion of any links does not necessarily imply a recommendation or endorse the views expressed within them.
Every effort is made to keep the website up and running smoothly. However, CLIN ® takes no responsibility for, and will not be liable for, the website being temporarily unavailable due to technical issues beyond our control.